How ABB uses ETAP and is-limiters to clear short-circuit constraints at DG cement

We selected ETAP and have used it extensively. We modeled the entire distribution system, from high-voltage grid infeed to low-voltage loads. ETAP’s analysing functions provided the results needed for the application engineering of the new and existing Is-limiters. This allowed us to keep fault currents below equipment ratings and protect the plant.
By Mr. Andreas Peters, Head of Business Development and Solution Marketing, ABB

DG Cement, a major cement producer in Pakistan, planned to expand an existing plant by adding a Waste Heat Recovery (WHR) plant and a separate unit with a 15 MVA generator. The existing network already included: Two 26 MVA transformers from the utility, on-site generators, two installed ABB Is-limiters (fault current limiters). The expansion significantly increased the short-circuit levels. Many switchgear panels were rated 31.5 kA / 40 kA with 100 kA peak capability; new fault levels would exceed those ratings without additional fault current limiting. ABB was tasked to: Perform a complete short-circuit study of the plant including the new WHR generator, design the application engineering for three Is-limiters (two existing, one new), determine tripping values and placement so that fault levels remain within equipment withstand limits for all operating scenarios.


Applying Fault Current Limiter in the DG Cement distribution network powered by two 26 MVA transformers

Challenges

  • Rising short-circuit levels due to added generation and network expansion, exceeding equipment ratings.
  • Need to limit fault current without the drawbacks of traditional reactors (voltage drop, losses, space).
  • Precisely calculating tripping values for Is-limiters, which depend on:
    • Fault location
    • Network impedance
    • Operating configuration (generators / ties in or out)
  • Ensuring that in every operating scenario, for any short-circuit location, at least one Is-limiter operates fast enough to protect the system.
  • Performing all studies according to IEC 60909 and internal ABB standards.

 

ABB is-limiter technology (Why FCL instead of reactors or breakers?)

  • A fault current limiter (FCL) is required when calculated fault levels exceed equipment withstand ratings.
  • Traditional reactors limit current but cause continuous voltage drop, losses and occupy valuable space.
  • A standard circuit breaker typically clears faults in 45–120 ms (relay + breaking time), long enough for the first current peak to reach the destructive zone.
  • ABB’s Is-limiter detects faults in microseconds and interrupts in roughly 5–10 ms, so the first peak never reaches the destructive zone.
  • Internally, it acts like an intelligent fuse: a hollow conductor with a charge element and a parallel fuse. When the control unit decides to trip, the charge opens the conductor and the current transfers to the fuse, which then melts and isolates the phase.
This ultra-fast clearing time makes Is-limiters an elegant, efficient solution for DG Cement.

Which solutions did they choose?

Selected applications

ABB used ETAP 19.5 extensively:

IEC 60909 short-circuit analysis

  • Full digital twin of the plant from high-voltage grid to low-voltage loads
  • Short-circuit duties at all buses, with and without Is-limiters in service

Scenario & study wizard

  • Automation of 26 operating scenarios (different generator combinations, tie-switch states, etc.) and multiple fault locations
  • Rapid identification of which buses exceed their fault-current withstand ratings in which scenarios

Configuration manager

  • Visualization of which Is-limiter is in service in each configuration and how it splits the system (blue / red / grey areas)
  • Understanding which Is-limiter can effectively reduce fault current for a given fault location

Custom post-processing (tripping-value calculation)

  • For each scenario and fault location, read fault level at the bus and contribution through the Is-limiter
  • Apply the proportion method to compute the required tripping value so that resulting current stays within switchgear capability

 

How ABB determined tripping values with ETAP

Determine fault contribution through the limiter path

  • Example: for a bus fault, total prospective current is 60 kA, of which 30 kA flows through the Is-limiter → 50% contribution.

Consider downstream impedance

  • If cable impedance reduces total fault to 40 kA, contribution through Is-limiter is still ~50% → 20 kA.

Use ETAP results to populate the equation

  • Scenario 18, fault at a 31.5 kA / 80 kA peak bus:
    • Total fault level: 46.276 kA
    • Contribution via Is-limiter 1: 28.366 kA
    • Equipment withstand: 31.5 kA
    → Calculated tripping value ≈ 19.3 kA
  • Scenario 14, same fault location, different generators in service:
    • Total fault: 31.778 kA
    • Contribution via Is-limiter: 12.722 kA
    → Tripping value ≈ 12.6 kA

Repeat for all scenarios and all buses

  • For every operating configuration and every potential fault location, ABB computed the required tripping value.

Choose the smallest tripping value

  • The final setting for each Is-limiter is the minimum of all calculated values → guarantees safe operation in any configuration.

Why do they use ETAP?

Main customer benefits

  • Safe fault levels: short-circuit currents are limited below the 31.5 kA / 40 kA equipment rating and 80–100 kA peak withstand limits
  • High selectivity and speed: Is-limiters clear faults in 5–10 ms, avoiding destructive peaks while leaving normal operation unaffected
  • Comprehensive coverage: protection is valid for all 26 operating scenarios and every bus, thanks to ETAP’s automated studies
  • Efficient engineering process: ETAP’s Scenario & Study Wizard and Configuration Manager drastically reduced manual work for ABB engineers
  • Future-proof approach: lessons learned are being used to develop an ETAP library component for ABB fault current limiters, which will simplify planning and protection studies for future projects

What do they think about ETAP?

Customer perspective

Fault current limiter application engineering is a complex task that depends heavily on operating scenarios and fault locations. ETAP’s automation allowed us to handle 26 operating scenarios, calculate tripping values for each Is-limiter and each bus, and ultimately choose safe settings that keep DG Cement’s equipment protected in every case.
By Andy Peters, Head of Product Development, ABB



Videos

ABB FCL Application Engineering for IS-Limiters

This presentation will feature covert ABB Fault Current Limiter (FCL) application engineering for Is-limiters. We will explain the fault current limiter technology by using the well-known ABB FCL Is-limiter. The FCL technology will be introduced, how it clears a short-circuit fault current compared to a standard circuit breaker, and the major components of an FCL. The theory of the application engineering process and the calculation of the tripping value for an FCL will be introduced. Based on an actual customer project, it will be shown how ETAP has facilitated the complex FCL application engineering, and examples will be provided of how the real tripping value for a fault current limiter is determined. The session will conclude with an overview of how etap can already be used today for an FCL application engineering and what will be enhanced in the future.


Solutions


Packages/Products